Skip to content ⚡ NEW · Free Battery Backup Calculator — built on real lab discharge tests →
Su-vastika — A Rotomag Company
Heavy Duty IGBT UPS

Heavy Duty UPS 1P-1P 15KVA / 180V

[av_section min_height=” min_height_pc=’25’ min_height_px=’500px’ padding=’small’ custom_margin=’0px’ custom_margin_sync=’true’ svg_div_top=” svg_div_top_color=’#333333′ svg_div_top_width=’100′ svg_div_to

About This Product







MODEL & RATING
Model Name Static UPS 15KVA/180V 1P-1P
Rating 15KVA (1P-1P)
Nominal Battery Voltage 180VDC
Specified Load 12KW (1P-1P)
Mains Input Range Mains AC low cut 140VAC±10V
Mains AC low-cut recovery 150VAC ± 10V
Mains AC high cut 270VAC±10V
Mains AC high-cut recovery 260VAC ± 10V
Frequency Bypass range 50Hz ± 10%
Output Mains Mode Voltage Window Same as Input
Output Backup Mode Wave Form Pure Sinewave
Frequency 50 ± 0.1 Hz
THD Resistive load 5%
Regulation 220V± 15%
Peak Efficiency at Resistive Load >88%
Battery Battery Types (User Selectable) Tubular/SMF/LA
Charging Current 7A-20A ± 10%
Battery Charger Boost Voltage 208V ± 1V
Max. Battery Charger Float Voltage 204 ± 1V
Battery Low Cut Warning at Rig terminal 162V ± 1V
Battery Low Cut Point 160V ± 1V
Transfer Time Backup to Mains ≤3msec
Protection Over Load in backup mode 110%-125% 5 MIN
125%-150% 2 MIN
150%-175% 15 SEC
110%-125% 5 MIN
200%___3SEC
300%___1SEC
Short circuit (300% Load) Yes
Fan fail protection (Thermal protection) Yes
Battery deep Discharge (<225VDC ± 2V) & Over Charge (>150VDC ± 2V)
Protection
Yes (via Battery Low Cut / High Cut)
Short Circuit at Input Side Input MCB Trip
Cold Start (Inrush Load) 12KW 12KW (67A ± 2A DC Current)
Noise Acoustic noise at 1meter (<60dB)
Environment Operating Temperature 0°C TO 50°C
Storage Temperature 0°C T O 50°C
Operating Relative Humidity 90% non-condensing
Earth Leakage Current In Mains mode at Input 280V & full load condition. less than 2.5mA
In backup mode at full load condition. less than 2.5mA
IR Test (Type Test) Between Input+ Output & Earth at 1kVDC. The
result must be > 1GΩ
2.2 GΩ@1KV
High voltage test (Type Test) Input + Output to Earth at 5KV for 1minute,
Leakage current less than 3mA
OK
Graphical LCD
Messages & Alarms
Messages Alarms
Mains Mode: Mains Input Voltage, Battery
percentage, Ambient temperature.
Back-up Mode: Mains Input Voltage, Battery
percentage, Load percentage, Ambient
temperature
LCD firmware Version and UPS Software
Version
Mains MCB Trip, Battery low warning,
Battery Low Shutdown, Battery High
shutdown, Overload warning, Overload
shutdown, short circuit shutdown, Hightemperature warning, High Temperature
shutdown, Mains high voltage, Mains low
voltage, Communication error
Messages in Abnormal Operating Conditions:
Overload protection Indication Overload + Buzzer beep
Short circuit protection Indication Short circuit + Buzzer beep
Back feed protection Indication Short-circuit + Buzzer beep
Battery Reverse Connection DC Fuse will blow (the system will recover after replacement of DC Fuse).
ON/OFF Switch Inverter ON/OFF control via Puss Switch on Front Panel



Su-vastika Heavy Duty UPS (IGBT Based) 1P-1P, also known as Industrial UPS, runs heavy, mechanical and Inductive, Capacitive, Resistive or mixed loads. The major differentiating factor of Su-vastika Heavy Duty UPS is that it uses advanced Static switches that reduce switching time to just ≤ 5milli seconds, fast enough to prevent a computer and most sensitive equipment from resetting.

Because of its strong R&D and the experience of its able Mentor Mr. Kunwer Sachdev, Su-vastika understands the power backup needs of its customers across industries, and, most importantly, it’s our Patented Technology as well.

We have designed a range of state-of-the-art Heavy-Duty UPS starting from 7.5KVA to 15KVA (1P:1P) that provides.

  • Protection of your machinery/appliances during power surges
  • High energy storage
  • Fast switching technology
  • Negligible maintenance cost
  • Lifelong usage with long-lasting batteries

Our Heavy-Duty UPS range is used in almost every industry, from the hospital to the IT industry.

Functional areas of  Heavy Duty UPS are:

  • Schools/Education Facilities
  • Gyms and Health Clubs
  • Multiple Floor Houses
  • Showrooms
  • Coffee Shops