Skip to content ⚡ NEW · Free Battery Backup Calculator — built on real lab discharge tests →
Su-vastika — A Rotomag Company
Heavy Duty IGBT UPS

Heavy Duty UPS 1P-1P 7.5KVA / 96V

[av_section min_height=” min_height_pc=’25’ min_height_px=’500px’ padding=’small’ custom_margin=’0px’ custom_margin_sync=’true’ svg_div_top=” svg_div_top_color=’#333333′ svg_div_top_width=’100′ svg_div_to

About This Product









MODEL: Inverter 7.5KVA/72V 1P-1P (IGBT Based)
Parameters Specified Value
Capacity 7.5KVA (1P-1P)
Nominal Battery Voltage 72VDC
Specified Load 6KW (1P-1P)
Mains Input Range Mains AC low cut
Mains AC low cut recovery
Mains AC high cut
Mains AC high cut recovery
Frequency Bypass range:
140VAC±10V
150VAC ± 10V
280VAC±10V
270VAC ± 10V
50Hz ± 10%
Output Mains Mode Voltage Window Same as Input
Output Backup Mode Wave Form
Frequency
THD Resistive load
Regulation
Peak Efficiency at Resistive load
Pure Sinewave
50 ± 0.1 Hz
<5%
220V± 15%
>80%
Battery Battery Types (User Selectable) Tubular/SMF/LA
Charging Current 3A-20A ± 10%
Low Battery Warning 64.8V ± 0.5V
Low Cut Battery 61.4V ± 0.5V
Battery Boost Charging Voltage 86.4V ± 0.5V
Battery Float Charging Voltage 82.2V ± 0.5V
Battery Float Charging Voltage 27.2V ± 0.2V TUB/SMF
Transfer Time Backup to Mains ≤40msec
Protection Over Load in backup mode 110%-125% 5 MIN
125%-150% 2 MIN
150%-175% 15 SEC
200%___3SEC
300%___1SEC
Short circuit (300% Load) Yes
Fan fail protection (Thermal protection) Yes
Battery deep Discharge (<60VDC ± 0.5V) & Over Charge (>90VDC ± 0.5V)
Protection
Yes (via Battery Low Cut / High Cut)
Short Circuit at Input Side Input MCB Trip
Cold Start (Inrush Load) 6KW 6KW (84A ± 2A DC Current)
Noise Acoustic noise at 1meter <60db
Environment Operating Temperature:
Storage Temperature:
Operating Relative Humidity:
0°C TO 50°C
0°C TO 50°C
90% non-condensing
Earth Leakage Current In Mains mode at Input 280V & full load condition <2.5mA
In backup mode at full load condition. <2.5mA
High Voltage Test (Type Test) Input + Output to Earth at 5KV for 1minute, Leakage current <3mA OK
IR Test Input + Output to Earth at 5KV for 1minute, Leakage current <3mA 2.2 GΩ@1KV
Graphical LCD Messages & Alarms Messages Alarms
Mains Mode: Mains Input Voltage, Battery percentage, Ambient
temperature. Back-up Mode: Mains Input Voltage, Battery percentage, Load
percentage, Ambient temperature LCD firmware Version and UPS Software
Version
Mains MCB Trip, Battery low warning, Battery Low Shutdown, Battery High
shutdown, Overload warning, Overload shutdown, short circuit shutdown,
High temperature warning, High Temperature shutdown, Mains high voltage,
Mains low voltage, Communication error
Messages in Abnormal Operating Conditions:
Overload protection Indication Overload + Buzzer beep
Short circuit protection Indication Short circuit + Buzzer beep
Back feed protection Indication Short circuit + Buzzer beep
Battery Reverse Connection DC Fuse will blow (the system will recover after the replacement
of the DC Fuse).
ON/OFF Switch Inverter ON/OFF control via Puss Switch on Front Panel



Su-vastika Heavy Duty UPS (IGBT Based) 1P-1P, also known as Industrial UPS, runs heavy, mechanical and Inductive, Capacitive, Resistive or mixed loads. The major differentiating factor of Su-vastika Heavy Duty UPS is that it uses advanced Static switches that reduce switching time to just ≤ 5milli seconds, fast enough to prevent a computer and most sensitive equipment from resetting.

Because of its strong R&D and the experience of its able Mentor Mr. Kunwer Sachdev, Su-vastika understands the power backup needs of its customers across industries, and, most importantly, it’s our Patented Technology as well.

We have designed a range of state-of-the-art Heavy-Duty UPS starting from 7.5KVA to 15KVA (1P:1P) that provides.

  • Protection of your machinery/appliances during power surges
  • High energy storage
  • Fast switching technology
  • Negligible maintenance cost
  • Lifelong usage with long-lasting batteries

Our Heavy-Duty UPS range is used in almost every industry, from the hospital to the IT industry.

Functional areas of  Heavy Duty UPS are:

  • Schools/Education Facilities
  • Gyms and Health Clubs
  • Multiple Floor Houses
  • Showrooms
  • Coffee Shops